Product Description
The Cat® spark-ignited generator product line for stationary applications feature permanent magnet excitation, amortisseur winding, skewed stator, voltage adjustment through the EMCP controller, Class H winding insulation and 2/3 pitch incorporated.
Generator Set Specifications
- Frequency
- 60 Hz
- Natural Gas Rating
- 250 eKW
- Emissions/Fuel Strategy
- U.S. EPA Certified for Non-Emergency Application
- Displacement
- 864.7in³
- Speed
- 1800 rpm
Engine Specifications
- Fuel System
- Carbureter, Down Draft
- Aspiration
- Turbocharged - Aftercooled
- Compression Ratio
- 9.5:1
- Bore
- 5.31in
- Stroke
- 6.5in
Generator Set Dimensions
- Length
- 138.74in
- Width
- 57.6in
- Height
- 68.04in
- Weight
- 6364lb
Standard Equipment
-
- Cooling
-
- Factory-installed radiator
- Closed coolant recovery system
- 50/50 Ethylene glycol antifreeze
- Standard ambient temperatures up to 50°C (122°F)
- Radiator and cooling fan complete with protective guards
-
- Air Inlet
-
- Single element air filter
-
- Fuel
-
- Low fuel pressure switch
- Fuel pressure test po
- Primary and secondary fuel shut-off
- Dual lock off valves
- NPT connection
- Natural Gas or LP Vapor
-
- Generator
-
- Class H insulation material
- Full load capacity alternator
- Permanent magnet excitation
- Full load capacity alternator
- Permanent magnet excitation
- Matched to the performance and output characteristics of Cat engines
- Integrated Voltage Regulator
- Class H insulation material
- IP23 Protection
-
- Exhaust
-
- Exhaust outlet with 3” pipe
-
- Controls
-
- EMCP 4.2 Series generator set controller
-
- Mounting
-
- Vibration isolaton (puck type)
- Rubber vibration isolators
-
- Electric Starting And/or Prelube
-
- Solenoid activated starter motor
- Engine electrical system
- Battery cables
- Solenoid activated starter motor
-
- Electric Power - Package Serial Number Prefix
-
- Battery charging alternator
-
- Governor
-
- Electronic governor (non adjustable)
-
- Control Panel
-
- EMCP 4.2 Series generator set controller
-
- Starting/charging
-
- 12 volt starting motor
- Batteries with rack and cables
Optional Equipment
-
- Starting/charging
-
- Battery heater
- Battery charger – UL Listed 10 amp
- Jacket water heater
- Charging alternator
-
- General
-
- CSA Certification
- Suitable for Use as Service Equipment (SUSE)
- UL 2200 package
- Enclosures: sound attenuated, weather protective
- Automatic transfer switches (ATS)
-
- Generator
-
- Shunt trip and auxiliary contact breaker
- Anti-condensation heater
- Thermal magnetic or electronic trip MCCBs
- Oversize and premium generators
- Excitation: [ ] Permanent Magnet Excited (PM)
- Anti-condensation heater