D450 GC (60 Hz) Generator Set

Product Description

The D450 GC diesel generator sets have been developed to meet your needs in standby applications. Producing reliable power of 450 ekW at 60 Hz, meeting ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. The engines are certified for U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 or Tier 3 Nonroad Equivalent Emission Standards).

Generator Set Specifications

Maximum Rating
450 ekW
Minimum Rating
450 ekW
Emissions/Fuel Strategy
EPA Stationary Emergency
Voltage
480 to 600 Volts
Frequency
60 Hz
Speed
1800 RPM
Duty Cycle
Standby

Engine Specifications

Engine Model
Cat® C15 In-line 6, 4-cycle diesel
Bore
5.4in
Stroke
6.8in
Displacement
928in³
Compression Ratio
16.1:1
Aspiration
Turbocharged Air-to-Air Aftercooled
Fuel System
MEUI
Governor Type
ADEM™A4

Generator Set Dimensions

Length - Maximum
189.6in
Width - Maximum
64.2in
Height - Minimum
80.1in
Height - Maximum
101.7in
Dry Weight - Genset (minimum)
8172.5lb
Dry Weight - Genset (maximum)
10238.3lb

Standard Equipment

  • Air Inlet System
    • Aftercooler core
    • Turbocharger
    • Air cleaner - Non canister, disposable
  • Control Panel
    • GCCP 1.2
  • Cooling System
    • Thermostats and housing
    • Blower fan and fan drive with guards
    • Radiator, package mounted
    • Coolant drain valve
    • Jacket water pump, gear driven, centrifugal
    • Radiator sight gauge
  • Exhaust System
    • Exhaust manifold - dry
  • Fuel System
    • Fuel priming pump
    • Integral tank base, 24 hours, UL142
    • Primary fuel filter w/integral water separator and secondary filter, spin on
    • Engine fuel transfer pump
    • Fuel cooler
  • Generator Set
    • Complete system designed & built at ISO 9001:2000 certified facilities
    • Factory tested to design specifications at full load conditions
    • All protective devices and control functions simulated and checked
  • Generators And Generator Attachments
    • IP23 Protection
    • Voltage regulator (single phase sensing)
    • Easy access to AVR and terminals
    • Brushless, self-excited 2/3 pitch (600V uses Internal excitation (IE))
    • Terminal box, IP22 RHS facing, bottom cable entry
    • Standard winding protection for non-harsh environments with relative humidity ? 95%
    • 6 Leads
    • Insulation system, Class H
  • Governing System
    • Cat electronic governor (ADEM A4)
  • Lube System
    • Fumes disposal to front of radiator
    • Oil filter, spin on
    • Lubricating oil, CK-4 (10W-30)
    • Shallow oil pan
    • Oil cooler
    • Oil filler and dipstick
    • Oil drain with valve
  • Mounting System
    • Includes lifting provisions and termination points for coolant and lube oil drain lines
    • Captive linear vibration isolators between base and engine-generator
  • Protection
    • Safety shutoff - Low oil pressure
    • Safety shutoff - Overspeed
    • Safety shutoff - High water temperature
  • Starting/charging System
    • 24-volt electric starting motor
    • 24V, 45 Amp Charging alternator
  • General
    • Vibration damper
    • Parts book
    • Lifting eyes

Optional Equipment

  • Air Inlet System
    • Air cleaner (Non canister disposable)
  • Bases, Mounting & Fuel Tanks
    • Overfill prevention valve
    • Wide Base - Skid
    • Audio & visual fuel alarm (@90% fuel level)
    • Integral tank base, 24 hours, UL142
    • Fuel tank pill pipe & lockable cap
    • 5 Gallon Spill Containment
  • Exhaust
    • Industrial, residential, critical mufflers
  • Circuit Breaker
    • 400A LSI
    • 400A LS/I
    • 800A LSI
    • Auxiliary contacts
    • 600A LS/I
    • 1200A LSI
    • 600A LSI
    • 1200A LS/I
    • 800A LS/I
  • Control System
    • Volt free contacts
    • 100A Load center
    • Product link remote monitoring hardware
    • Twist release, Red button emergency stop
    • 16 -light NFPA 99/110 Annunciator
    • 20A GFCI (Ground Fault Circuit Interrupter)
    • Audible alarm Gp
    • Ground fault relay
  • Enclosures
    • E-Stop
    • AC & DC Source lights
    • Sound attenuated Level 2 enclosure (White)
  • Generator
    • Anti-condensation heater
    • Oversize and premium generators
    • Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
    • Permanent magnet excitation (PMG) generator
    • Space heater
  • Exhaust System
    • Manifold and turbocharger guards
    • Flexible exhaust connection
    • 8" Muffler - 25 dBA attenuation
  • Starting System
    • Standard battery set: 1000 CCA, 90 amp/hr.
    • Oversize battery set, 1400 CCA, 200 amp/hr
    • Battery charger (UL Certified)
    • Jacket water heater
  • Power Termination
    • Circuit breakers, IEC compliant
    • Circuit breakers, UL listed
  • General
    • UL2200 Certification
    • CSA Certification
    • Extended Service Coverage
    • Generator test report
    • CSA Certification
    • UL 2200 package
  • Lube System
    • Manual sump pump
  • Mounting System
    • Narrow skid base - replaces standard fuel tank base