Product Description
From natural gas-fueled combined heat and power (CHP) systems and emergency power for facilities, to renewable biogas energy to support the local grid, or electricity generated from coal mine gases, Caterpillar has a wide range of reliable gas power solutions.
Generator Set Specifications
- Continuous Rating
- 2050 ekW
- Fuel Type
- Natural Gas, Biogas, Coal Gas
- Maximum Electrical Efficiency
- 40.10%
- Maximum Standby Rating
- 2050
- Frequency
- 50 / 60 Hz
- RPM
- 1200 / 1500 / 1800 rpm
Engine Specifications
- Engine Model
- G3520C
- Displacement
- 5270in³
- Aspiration
- TA
- Bore
- 6.7in
- Stroke
- 7.5in
- Fuel System
- Natural Gas, Biogas, Coal Gas
- Compression Ratio
- 11.3
Generator Set Dimensions
- Length
- 249in
- Width
- 79in
- Height
- 92in
- Dry Weight - Genset
- 37959lb
- Weight
- 37953lb
Standard Equipment
-
- Air Inlet
-
- Two-element single-stage air cleaner with enclosure and service indicator
-
- Control Panels
-
- EMCP 4.3
-
- Cooling
-
- ANSI Class 6 in/DN customer flange connections for JW inlet and outlet
- Engine driven water pumps for jacket water and aftercooler
- 2nd Stage SCAC-Cat Flange
- Jacket water and SCAC driven pumps
- Jacket water and SCAC thermostat and outlet--ANSI 6 in/DN150
-
- Exhaust
-
- Dry exhaust manifolds, insulated and shielded
- Cat-flanged face outlet on turbocharger
- Individual exhaust port and turbocharger outlet wired to Integrated Tmeperature Sensing Module (ITSM) with GECM providing alarms and shutdowns
-
- Fuel System
-
- Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
- Electronic fuel metering valve, ANSI flange
- Throttle plate, 24V DC actuator, controlled by GECM
- 24V ETR Gas Shutoff Valve
-
- Ignition System
-
- Electronic Ignition System (controlled by GECM)
- Individual Cylinder Detonation Sensitive Timing (DST)
-
- Generator
-
- 3-phase brushless, salient pole
- Class F Insulation & temperature rise
- Reactive droop
- Permanent Magnet Excitiation
- Winding temperature detectors
- Anti-condensation space heater
- SR4B or SR5
- Busbar connections
- Caterpillar's Digital Voltage Regulator (CDVR) with 3-phase sensing and KVAR/PF control
- SR4B
-
- General
-
- Crankshaft Vibration Damper and Guard
- RH Service
- Parts Book
- Operation and maintenance manuals
- Paint - Caterpillar Yellow except rails and radiators gloss black
Optional Equipment
-
- Air Inlet
-
- Enclosure Mounting Brackets and Piping
- Mounting stand
- Air cleaner with precleaner
-
- Contol Panel
-
- Custom 8-Light Alarm Module
- Local NFPA99-110 Alarm Module w/LEDs
- Remote 24-32V 8/16 Annunciator
- Synchronizing Module
- PL1000E/PL1000T Communications Module
- Engine Failure Relay
-
- Control Panels
-
- Local alarm module
-
- Cooling
-
- Inlet/Outlet connections
- Engine pumps
- Aftercooler air lines, aftercooler core replacement
- Jacket water coolant heater
-
- Exhaust
-
- Mufflers (15/18/25 dBA Attenuation) and spark-arresting muffler with ANSI companion flanges
- Exhaust expanders
- Flexible fittings
- 305/360/406 mm Elbow Kits
-
- Fuel System
-
- 14-69 kPa (2-10 psi) gas pressure regulator
- Fuel filter
- 24V DC Gas shutoff valve
- 207-276kPa, 30-40 psi gas knockdown regulator
-
- Generator
-
- Generator Removal
- Annunciator Modules
- Medium and high voltage generators and attachment
- 60 Hz--480/4160 Volt Generator Options
- Cable access box
- Generator air filter
- European Bus Bars
- Low voltage extension box
- Bearing temperature detectors
- 8.7/15 kV Class Current Transformers (CCCT, DCT, CT)
- 50 Hz--3300/6600 Volt Generator Options
-
- Governing System
-
- Load share module
-
- Starting/charging
-
- Jacket water heater
- Battery diconnect switch
- 24V starting motors
- Battery with cables and rack (shipped loose)
- 60A, 24V charging alternator (requires engine driven pumps)