Product Description

This XQP100 generator set provide low fuel consumption performance. With a robust, rental or mobile-ready construction, the product line is designed to be easily transported around project sites safely and efficiently. Heavy-duty bases with integrated fork lift pockets allow the unit to be dragged and lifted with ease, while Clipsal or CEE socket options are available on select models to reduce installation time and provide trouble-free power distribution.

Generator Set

Rating Prime
100 kVA
Frequency
50/60 Hz
Voltage
127 - 480 V

Engine

Engine
Cat C4.4
Fuel
Diesel

Dimensions

Width
44.1in
Height
72.7in
Length
109.1in
Weight - With Lube Oil and Coolant
4469lb

Fuel Consumption EU Stage IIIA

100% Load 50Hz
6.2gal/hr
100% Load 60Hz
7.3gal/hr
75% Load 50Hz
5.4gal/hr
75% Load 60Hz
5.9gal/hr
50% Load 50Hz
3.9gal/hr
50% Load 60Hz
4.2gal/hr

Fuel consumption Best Fuel Efficiency

100% Load 50Hz
6gal/hr
100% Load 60Hz
7.1gal/hr
75% Load 50Hz
4.5gal/hr
75% Load 60Hz
5.3gal/hr
50% Load 50Hz
3.1gal/hr
50% Load 60Hz
3.7gal/hr

Noise rating (with enclosure) EU Stage IIIA

Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
77.5 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
79.5 dB(A)

Noise rating (with enclosure) Best Fuel Efficiency

Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
80.3 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
81.6 dB(A)

Standard Equipment

  • Cat C4.4 Diesel Engine
    • Turbocharged
  • Generator
    • LC3114F Frame
  • Air Filter
    • Cyclonic/paper with dust cup and service indicator
  • Cat Connect Remote Monitoring
    • Provides package monitoring and management
  • Cooling System
    • Package mounted radiator with vertical air discharge. Filled from factory
  • Charging / Starting System
    • 12V heavy duty starting motor and charging alternator c/w battery isolator
  • Fuel System
    • 24 hour dual wall fuel tank with 3 way directional valve for external supply
  • Control Panel
    • Digital XQCP set mounted controller
  • Distribution
    • Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
  • Structure
    • Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. base frame is wider than enclosure to protect generator set during transportation.
  • Enclosure
    • Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
  • Exhaust
    • Integrated spark arresting silencer
  • Lube Oil
    • On engine primary and secondary oil filters. Filled from factory
  • General
    • Factory tested and inspected