Product Description
The C13 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 320 to 400 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. Our C13 generator sets are certified to Low Fuel Consumption Emissions / Fuel Strategy.
Generator Set Specifications
- Maximum Rating
- 400 ekW
- Minimum Rating
- 320 ekW
- Emissions/Fuel Strategy
- EPA Stationary Emerg Use
- Voltage
- 208 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- C13 ACERT In-line 6, 4-cycle diesel
- Bore
- 5.12in
- Stroke
- 6.2in
- Displacement
- 763in³
- Compression Ratio
- 16.3:1
- Aspiration
- Turbocharged Air to Air Aftercooled
- Fuel System
- MEUI
- Governor Type
- Adem™A4
Generator Set Dimensions
- Length - Maximum
- 186.7in
- Width - Maximum
- 79.3in
- Height - Maximum
- 84in
Standard Equipment
-
- Air Inlet System
-
- Turbocharger
- Aftercooler core
- Air cleaner; light duty with disposable paper filter
-
- Starting / Charging
-
- Charging alternator
- 24 Volt electric starting motor
-
- Control Panel
-
- GCCP 1.3
-
- Control System Controller
-
- GCCP 1.3
-
- Cooling System
-
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
- Coolant drain line with valve
- Radiator and cooling fan with guard
-
- Certification
-
- EPA stationary emergency use
-
- Exhaust System
-
- Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
-
- Base / Fuel Tank
-
- Audio and visual fuel alarm
-
- Fuel System
-
- Standard open set fuel tank/base supplied
- Base, formed steel with single wall integral 8-hour fuel tank
-
- Protection
-
- Safety shutoff - Overspeed
- Safety shutoff - Low oil pressure
- Safety shutoff - High water temperature
-
- Generator And Attachments
-
- Segregated low voltage (AC/DC) wiring panel
- Power center, IP22
- A Frame generator - IP21 Protection
- Integrated voltage regulator (IVR)
- Optional LC Frame generator - IP23 Protection
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
-
- Governing System
-
- Cat electronic governor (ADEM A4)
-
- Lube System
-
- Oil cooler
- Oil drain valves
- Lubricating oil
-
- Mounting System
-
- Includes lifting provisions and termination points for coolant and lube oil drain lines
- Captive linear vibration isolators between base and engine-generator
-
- Starting / Charging System
-
- 24V battery with rack and cables
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment
-
- European Certificates
-
- Global Certification for CIS
- EU Certificate of Conformance (CE)
-
- Air Inlet System
-
- Single element air cleaner
- Dual element air cleaner
-
- Circuit Breakers
-
- Padlockable circuit breaker device
- 3 Pole (IEC-100% rated) Circuit breaker
- Shunt trip for IEC circuit breaker
- 4 Pole (IEC-100% rated) Circuit breaker - Motorised
- Circuit breaker (IEC) Auxiliary contacts
- 4 Pole (IEC-100% rated) Circuit breaker
- Power terminal strip
- 3 Pole (IEC-100% rated) Circuit breakers - Motorised
-
- Control Panels
-
- Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
- GCCP 1.4
- Volt free contacts
- Local alarm modules: Local annunciator
- Remote annunciator module
-
- Cooling System
-
- Radiator duct flange
- Stone guards
- Low coolant temperature alarm
-
- Enclosures
-
- Sound attenuated enclosures
- High ambient sound attenuated enclosures
-
- Exhaust System
-
- Flexible 8 inch exhaust fittings
- Mufflers - End in/end out
- 10, 25 and 35 dBA attenuation
- 6 and 8 inch elbow kit
- 6 and 8 inch flange GP
-
- Fuel System
-
- Fuel transfer system controls
- Manual fuel transfer pump
- Integral dual wall fuel tank base
-
- Generator And Attachments
-
- LC frame generator
- LC CIP generator
- Space heaters
- Ingress protection
- A Frame oversize generator
- Permanent magnet excitation (PMG) generator
- A Frame CIP generator
-
- Lube System
-
- Manual sump pump
-
- Mounting System
-
- Narrow skid base
-
- Starting / Charging System
-
- Battery disconnect switch
- Jacket water heater
- 5 Amp single Battery charger