Product Description
The XQ1140 offers multiple modes of operation to meet your unique needs – even as they change. By incorporating two C18, EPA Tier 4 Final compliant diesel generator sets, this package can provide power output from the generator sets in parallel, N+1 power or independent power from each generator set. That versatility minimizes your operating costs always with the XQ1140 reliability and durability.
Generator Set
- Rating Prime
- 910 ekW (1136 kVA)
- Frequency
- 60 Hz
- Voltage
- 120 - 600V
- Rating Standby
- 1000 ekW (1250 kVA)
Engine
- Engine
- Cat C18
- Fuel
- Diesel
Dimensions
- Height - Without Trailer
- 114in
- Length - Without Trailer
- 480in
- Width - Without Trailer
- 96in
- Weight with Lube Oil and Coolant, Without Trailer
- 50107lb
Fuel Consumption
- 100% Load 60Hz
- 66.4gal/hr
- 75% Load 60Hz
- 52.4gal/hr
- 50% Load 60Hz
- 38gal/hr
- 100% Load 60Hz
- 71.8gal/hr
- 75% Load 60Hz
- 56.6gal/hr
- 50% Load 60Hz
- 41gal/hr
Noise rating (with enclosure)
- Sound Power @ 7 meters (23 feet) @ All Ratings
- 76 dB(A)
Standard Equipment
-
- Cat C18 Diesel Engines
-
- Two Cat C18 Diesel Engines
- Reliable, rugged, durable design
- EPA Tier 4 Final and CARB Emissions Certified
- Turbocharged Aftercooled
- Aftertreatment module. DEF System
-
- Alternator And Alternator Attachments
-
- 3 Phase, brushless, 12 lead, Permanent Magnet Excited
- LC6134G Frame
- Anti-condensation space heaters
- Integrated voltage regulator (IVR) with VAR/PF control
- Sized for 105°C temperature rise at 40°C ambient
-
- Control Panels
-
- Dual EMCP 4.4 genset mounted digital controllers
- Externally accessible Color Touch-Screen HMI Control Center
- Manual and automatic paralleling capability
-
- Governing System
-
- Electrical governing system ADEM™ A4
-
- Cat Connect Remote Monitoring
-
- Provides package monitoring and management
-
- Cooling System
-
- Vertically mounted radiator with vertical airdischarge from the container
- Provides 47°C ambient capability at Prime rating
-
- Charging / Starting System
-
- UL Listed and CSA Certified 240V, 20 Amp battery charger
- Charging alternator; 24V-80A, heavy duty withintegral regulator and belt guards
- Solar maintainer for batteries
- Single electric starting motor, 24V per engine
-
- Fuel System
-
- 630-gal (2385 L) double-wall fuel tank, UL 142and ULC 601 Listed and complies with Transport Canada requirements, internal and external fuel fill
- Fuel tanks connected by fuel transfer system withfilter to allow both engines access to all fuel on-board
- Primary and secondary fuel filters
- Fuel cooler
-
- Air Inlet System
-
- Heavy-duty air element, canister type
-
- Distribution
-
- Externally accessible, Vibration Isolated, 3600A Frame, 1000 Ka, IC, 3-pole electrically operated breaker with lock out tag out provision
- Busbar connections
- Dual customer connections
-
- Sound Attenuated Container
-
- 40' ISO high cube container
- Sound level is 76 dB(A) at 7 meters per SAEJ1074 measured at 75% prime load
- Sound attenuated air intake louvers and fivelockable personnel doors with panic release
-
- Lube System
-
- Pump, integral oil cooler, lube oil, filter, filler and dipstick, and oil sampling valve
- Oil drain line with internal brass ball valve routedto connection point accessible from exterior
-
- General
-
- Factory tested and inspected
- Full manufacturer's warranty
- UL, NEMA, ISO, and IEEE standards
Optional Equipment
-
- Trailer
-
- Two-axle, air-ride chassis with anti-lock brake system