C18 Generator Set

Product Description

The C18 diesel generator sets have been developed for your mission critical, standby and prime applications. Producing reliable power from 500 to 600 ekW at 60 Hz, meeting ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. Our C18 generator sets range from low fuel consumption systems to EPA Stationary Emergency (Tier 2) certified.

Generator Set Specifications

Maximum Rating
600 ekW
Minimum Rating
500 ekW
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
220 to 380 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime

Engine Specifications

Engine Model
C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
5.71in
Stroke
7.2in
Displacement
1106.4in³
Compression Ratio
14.5:1
Aspiration
Air to Air Aftercooled
Fuel System
Electronic unit injection
Governor Type
Adem™A4

Generator Set Dimensions

Length - Maximum
218.5in
Width - Maximum
80.9in
Height - Maximum
107.8in

Standard Equipment

  • Air Inlet
    • Air cleaner
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Fuel priming pump
    • Secondary fuel filters
    • Primary fuel filter with integral water separator
  • Generator
    • IP23 Protection
    • Matched to the performance and output characteristics of Cat engines
    • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
  • Power Termination
    • Busbar
  • Control Panel
    • GCCP 1.3
  • Mounting
    • Rubber vibration isolators
  • Starting/charging
    • 24 volt starting motor
    • Batteries
  • General
    • Paint - Caterpillar yellow except rails and radiators gloss black

Optional Equipment

  • Exhaust
    • Industrial, residential, critical mufflers
  • Generator
    • Anti-condensation heater
    • Oversize and premium generators
    • Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Control Panels
    • Remote monitoring software
    • Local & remote annunciator modules
    • Digital I/O module
    • GCCP 1.4
    • Load share module
  • Starting/charging
    • Oversize batteries
    • Battery chargers
    • Heavy duty starting system
    • Jacket water heater
    • Charging alternator
  • General
    • Narrow, wide or skid base
    • CSA Certification
    • UL 2200 package
    • EU Certificate of Conformance (CE)
    • Enclosures: Sound attenuated, weather protective
    • Single or dual wall integral fuel tanks
    • Integral & sub-base UL listed dual wall fuel tanks
    • Automatic transfer switches (ATS)
    • Sound attenuated, weather protective or high ambient weather protective enclosure
    • The following options are based on regional and product configuration:
    • Single or dual wall sub-base fuel tanks
    • EEC Declaration of Conformity
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007