C32 | 1250 kVA 50 Hz Generator Set

Product Description

Producing reliable power from 910 kVA to 1500 kVA at 50 Hz, our C32 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Our C32 generator sets are made for demands, so you can make yours.

Generator Set Specifications

Maximum Rating
1500 kVA
Minimum Rating
910 kVA
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Voltage
400 to 3300 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Engine Specifications

Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.71in
Stroke
6.38in
Displacement
1958.86in³
Compression Ratio
15.0:1
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
MEUI
Governor Type
Adem™A4

Generator Set Dimensions

Length - Minimum
164in
Length - Maximum
176.6in
Width - Minimum
66.3in
Width - Maximum
87.8in
Height - Minimum
85.1in
Height - Maximum
86.4in
Dry Weight - Genset (minimum)
14700lb
Dry Weight - Genset (maximum)
17855lb

Standard Equipment

  • Air Inlet System
    • Single element canister type with service indicator
  • Control Panel
    • GCCP Control panel
    • Control features
    • Programmable protective relaying functions
    • Digital indicators
    • Warning shutdowns
    • Communications
  • Cooling System
    • Fan and belt guards
    • Radiator fan and fan drive
    • ATAAC
    • Coolant drain line with valve
    • Caterpillar extended life coolant
    • Low coolant level sensor
  • Exhaust
    • Exhaust manifold - dry
    • 203 mm (8 in) ID round flanged outlet
  • Fuel System
    • Primary fuel filter with water separator
    • Fuel priming pump
    • Secondary fuel filters
    • Fuel cooler
  • Generators And Attachments
    • Integrated voltage regulator (IVR)
    • Permanent magnet excitation (PMG)
    • 3 Phase brushless
    • Reactive droop
    • Internal excitation (IE)
    • NEMA Class H insulation
    • Class H temperature rise at 40C ambient
    • Salient pole
    • Winding temperature detectors
    • 6 Lead
    • IEC standard hole pattern
    • Busbar connections, top center mounted, top cable entry
  • Governing System
    • ADEM(tm) A4
  • Mounting System
    • Rails - engine/generator/radiator mounting
    • Rubber anti-vibration mounts
  • Lube System
    • Oil drain lines and valve
    • Integral lube Oil cooler
    • Fumes disposal
    • Lubricating oil
    • Oil filter, filler and dipstick
    • Gear type lube oil pump
  • Power Termination
    • Busbar
  • Starting / Charging System
    • 24 Volt electric starting motor
    • Battery, rack and cables
    • Battery disconnect switch
    • 45 Amp Charging alternator
  • General
    • Caterpillar yellow with high gloss black rails & radiator
    • RH service
    • Flywheel and flywheel housing-SAE
    • SAE standard rotation

Optional Equipment

  • Air Inlet System
    • Dual element air cleaner
    • Heavy duty air cleaner
    • Standard air cleaners
  • Circuit Breakers
    • 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
    • Enclosures - Control packaging
    • Cable supports
    • Center posts busbars
    • Circuit breaker wiring groups
    • Power connection covers
    • Shrouds
    • 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
    • 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers
  • Control Panels
    • GCCP Control panel
  • Cooling System
    • Radiator duct flange
    • Certified radiator
    • High ambient radiator
    • Standard radiator
    • Extended life coolant
  • Enclosures
    • Enclosure fuel tank options
    • Sound attenuated enclosure
    • Enclosure louvres - fixed and motorized
    • Color options
    • AC Panel, outlets and lights
    • Premium sound attenuated enclosure
    • Cold weather bundle
    • Panel bracket
    • DC lighting package
  • Exhaust System
    • Exhaust through the wall kit
    • Flange and exhaust expanders
    • Flanges
    • Guard and shield system
    • All C32 engines have 203 mm (8 in) exhaust outlets
    • Elbow mounting kit
    • Mufflers
    • Flexible fittings
  • Generator And Attachments
    • Low voltage generators
    • Medium voltage generators
  • Lube System
    • Oil pan
    • Prelube manual sump pump
    • Oil level regulator
  • Mounting System
    • IBC vibration isolators
    • Mounting base types
    • Spring type vibration isolators
    • Standard package isolators
  • Power Termination
    • Circuit breakers, IEC compliant
    • Circuit breakers, UL listed
  • Power Connections
    • Low voltage connection cables
    • Neutral grounding connection
    • Center post busbars
  • Starting / Charging System
    • 10 Amp enclosure Battery charger
    • Space heater
    • 10 Amp Battery charger
    • 20 Amp Battery charger
    • 35 Amp Battery charger
    • Electric starting motor - Standard/heavy duty
    • Standard 24 volt open package battery set - Dry
    • Jacket water heater
  • Special Tests / Reports
    • PGS Test report @ 1.0 power factor
    • Standard engine test
    • Generator test report
    • Custom generator TVA report
    • PGS Test report @ 0.8 power factor
    • CSA test and certification
    • IBC seismic Certifications
    • Standard genset Torsional Vibration Analysis (TVA) report
    • OSHPD seismic Certifications
  • General
    • Special paint
    • US aid emblem