Product Description
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
- Maximum Rating
- 680 kVA
- Minimum Rating
- 680 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
- Voltage
- 380 to 415 Volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore
- 5.4in
- Stroke
- 6in
- Displacement
- 1648.86in³
- Compression Ratio
- 13:01
- Aspiration
- Turbocharged, Air to Air Aftercooled
- Fuel System
- Pump and Lines
- Governor Type
- ADEM™ A5
Generator Set Dimensions
- Length - Maximum
- 162.4in
- Width - Minimum
- 75in
- Width - Maximum
- 78.3in
- Height - Maximum
- 75in
- Dry Weight - Genset (minimum)
- 12039lb
- Dry Weight - Genset (maximum)
- 13030lb
Standard Equipment
-
- Air Inlet System
-
- Air cleaner, single element canister type with service indicator
-
- Control Panel
-
- GCCP Control panel
- Over/under voltage (27 / 59)
- Environmental sealed front face
- Generator phase sequence
- Communications
- Digital I/O module
- Features include:
- 2 Programmable relay outputs (Form C)
- Compatible with the following optional modules:
- Customer data link (Modbus RTU)
- 4 programmable relay outputs (Form A)
- Amps (per phase & average)
- kVA (per phase, average & percent)
- Text alarm/event descriptions
- Low coolant level
- Generator temperature monitoring module
- Run/auto/ stop/control
- Overspeed
- Serial annunciator module data link
- Emergency stop pushbutton
- Frequency (Hz)
- RPM
- 6 programmable digital inputs
- Oil pressure (psi, kPa or bar)
- Engine cycle crank
- Operating hours
- Local annunciator
- coolant temperature
- kW-hr (total)
- Programmable protective relaying functions:
- kW (per phase, average & percent)
- Low oil pressure
- Reverse power (kW) (32)
- Remote Serial annunciator
- DC volts
- Power factor (per phase & average)
- Remote CAN annunciator
- 24 Volt DC operation
- Accessory module data link
- Failure to start (overcrank)
- Over/under frequency (81 o/u)
- kVAr (per phase, average & percent)
- Warning/shutdown with common LED indication of shutdowns for:
- Low coolant temperature
- 2 Programmable digital outputs
- Reverse reactive power (kVAr) (32RV)
- Emergency stop
- Digital indication for:
- High coolant temperature
- Speed adjust
- Voltage adjust
- Volts (L-L & L-N)
- Overcurrent (50 / 51)
-
- Cooling System
-
- Fan and belt guards
- Coolant drain line with valve, piped to edge of base
- Caterpillar extended life coolant
- Coolant level shutdown
- Radiator with guard (Sized for 50 degrees C)
-
- Exhaust System
-
- Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
-
- Fuel System
-
- Flexible fuel lines terminated on base
- Fuel priming pump
- Primary and Secondary fuel filters
- Water seperator
-
- Generator And Attachments
-
- 3-phase sensing
- SR4B self excited
- Class H insulation
- 2:1 Volts/Hz
- Reactive droop
- VR6 voltage regulator
- Busbar termination
- Class F temperature rise
- 12 Leads
-
- Governing System
-
- Cat electronic governor
-
- Lube System
-
- Oil drain line with valve, piped to edge of base
- Lubricating oil
- Oil filter
- Fumes disposal, piped to front of radiator
-
- Mounting System
-
- Base, formed steel with linear vibration isolators between base and engine-generator
-
- Starting / Charging System
-
- Battery with rack, cables
- 45 amp Charging alternator
- 24 volt starting motor
- Fuel shutoff solenoid
Optional Equipment
-
- Air Inlet System
-
- Open element air cleaners
- Heavy duty air cleaners
- Dual element air cleaners
-
- Circuit Breakers
-
- 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
- 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
-
- Control Panel
-
- First local annunicators
- Local discrete I/O package
- Generator temperature monitoring package
- Ground fault relay
- Remote custom annunicator
- GCCP Control panel
- Generator running VFC
- GCCP Control panel
- Vandal proof panel door
- Common alarm/shutdown relay
-
- Cooling System
-
- Jacket water heaters
- Radiator duct flange
-
- European Certifications
-
- Eurasian Conformity (EAC) mark
-
- Exhaust System
-
- Elbow kit
- Manifold and turbocharger guards
- Through wall installation kit
- Mufflers
-
- Generator And Attachments
-
- Digital voltage regulator
- Oversize and premium generators
- Space heater
- Permanent magnet excitation (PMG)
-
- Lube System
-
- Manual sump pump
-
- Mounting System
-
- Fuel tank base (1200 ltr)
-
- Special Tests / Reports
-
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
-
- Starting / Charging
-
- Heavy duty starting system
- Battery chargers
- Battery disconnect switch
- Oversize batteries
-
- Governing System
-
- Electronic load share