Product Description
Producing reliable power from 2000 to 2500 kVA at 50 Hz, our 3516B diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. Generator sets offer both low fuel consumption and low emission systems.
Generator Set Specifications
- Standby Rating
- 2500 kVA
- Prime Power Rating
- 2275 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
- Voltage
- 380 to 11000 Volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Mission Critical, Prime, Continuous
- Maximum Rating
- 2500 kVA
- Minimum Rating
- 2000 kVA
Engine Specifications
- Engine Model
- 3516B TA, V-16, 4-Stroke Water-Cooled Diesel
- Bore
- 6.69in
- Stroke
- 8.46in
- Displacement
- 4764.73in
- Compression Ratio
- 15.5:1
- Aspiration
- TA
- Fuel System
- Electronic unit injection
- Governor Type
- Adem™3
Generator Set Dimensions
- Length - Minimum
- 233.4in
- Length - Maximum
- 251.7in
- Width - Maximum
- 90in
- Height - Maximum
- 93.2in
- Dry Weight - Genset (minimum)
- 31900lb
- Dry Weight - Genset (maximum)
- 40320lb
Standard Equipment
-
- Air Inlet
-
- Air cleaner
-
- Cooling
-
- Package mounted radiator
-
- Exhaust
-
- Exhaust flange outlet
-
- Fuel
-
- Secondary fuel filters
- Fuel priming pump
- Primary fuel filter with integral water separator
-
- Generator
-
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
-
- Power Termination
-
- Busbar
-
- Control Panel
-
- Cat ECS 100
-
- General
-
- Paint - Caterpillar yellow except rails and radiators gloss black
Optional Equipment
-
- Exhaust
-
- Exhaust mufflers (except Tier 4)
-
- Generator
-
- Permanent magnet excitation (PMG)
- Internal excitation (IE)
- Anti-condensation heater
- Oversize and premium generators
-
- Power Termination
-
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
-
- Control Panels
-
- Generator temperature monitoring & protection
- Digital I/O module
- Load share module
- EMCP 4.4
- Remote monitoring software
-
- Mounting
-
- Spring type vibration isolators
- IBC isolators
- Rubber anti-vibration mounts
-
- Starting/charging
-
- Oversize batteries
- Charging alternator
- Heavy duty starting system
- Jacket water heater
- Air starting motor with control and silencer
- Battery chargers
-
- General
-
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- EU Certificate of Conformance (CE)
- The following options are based on regional and product configuration:
- Enclosures: Sound attenuated, weather protective
- Automatic transfer switches (ATS)
- UL 2200 package
- Integral & sub-base UL listed dual wall fuel tanks
- Integral & sub-base fuel tanks
- EEC Declaration of Conformity
- CSA Certification