Product Description
Producing reliable power from 3150 – 4000 kVA in 50 Hz, our C175-20 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. The generator set is optimized for low fuel consumption or low emissions.
Generator Set Specifications
- Standby Rating
- 4000(no fan)/3900 kVA
- Prime Power Rating
- 3600(no fan)/3500 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
- Voltage
- 3300 to 11000 Volts
- Frequency
- 50 Hz
- Speed
- 1500 RPM
- Duty Cycle
- Standby, Mission Critical, Prime, Continuous
- Maximum Rating
- 4000 kVA
- Minimum Rating
- 3150 kVA
Engine Specifications
- Engine Model
- C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel
- Bore
- 6.89in
- Stroke
- 8.66in
- Displacement
- 6456.31in³
- Compression Ratio
- 15.3:1
- Aspiration
- Turbo Aftercooled
- Fuel System
- Common Rail
- Governor Type
- ADEM� A4
Generator Set Dimensions
- Length - Minimum
- 261.5in
- Length - Maximum
- 330.6in
- Width - Minimum
- 85.4in
- Width - Maximum
- 330.6in
- Height - Minimum
- 87.6in
- Height - Maximum
- 150.7in
- Dry Weight - Genset (minimum)
- 55100lb
- Dry Weight - Genset (maximum)
- 66200lb
Standard Equipment
-
- Air Inlet
-
- 4 x Single element canister air cleaners with service indicator(s).
-
- Control Panel
-
- Engine cycle crank
- Oil pressure (psi, kPa or bar)
- Digital Indicators
- Coolant temperature
- Environmental sealed front face
- Frequency (Hz)
- True RMS AC metering, 3-phase, +/-2% accuracy
- Text alarm/event descriptions
- Low coolant level
- Volts (L-L & L-N)
- Auto/start/stop control
- Warning/shutdown Indicators:
- Emergency stop pushbutton
- Engine cool-down timer
- DC volts
- High coolant temperature
- Operating hours
- Low oil pressure
- Cat ECS 100
- Amps (per phase & average)
- 4 Programmable relay Inputs
- Alarm acknowledge
- 4 Programmable relay output
- Failure to start (overcrank)
- Overspeed
- Lamp test
- 24 Volt DC operation
- Wall mounted controls
- RPM
-
- Cooling System
-
- SCAC cooling
- Coolant sensors
- JW Inlet: 6" ANSI / JW Outlet: 5" Cat Flange
- AC Inlet: 6" ANSI / AC Outlet: 3-1/2" ANSI
-
- Exhaust
-
- Dry exhaust manifold
- Bolted flange (ANSI 6" & DIN 150) with bellow for each turbo (Qty 4). 50 Hz
-
- Fuel
-
- Filters x 3
- Secondary/tertiary fuel filters
- 4 Micron spin on type
- 10 Micron spin on type
- Engine mounted filters x 3
- Primary fuel filter water/fuel water separator
-
- Generators And Attachments
-
- Salient pole
- RFI suppression
- Anti-condensation space heater
- IEC platinum Stator RTDs
- Form wound
- NEMA Class H insulation
- Voltage regulator
- Reactive droop capability
- Min/max Exciter limiter
- 3 Phase voltage sensing
- Exciter diode monitor
- 6 Leads
- 3 Phase brushless
- Right side extension box, bottom cable entry
- Permanent magnet excitation (PMG)
- Class H temperature rise at 40C ambient
-
- Governing System
-
- ADEM A4
- Redundant shutdown (Overspeed protection through a duplicate speed sensing system)
-
- Lube System
-
- Oil drain lines and valve
- Gear type lube oil pump
- Oil filter, filler and dipstick
- Integral lube Oil cooler
- Lubricating oil
- Fumes disposal
-
- Mounting Systems
-
- Rails - Engine/Generator
- Rubber anti-vibration mounts - shipped loose
-
- Starting / Charging System
-
- Batteries and battery rack w/cables
- Dual 24 volt electric starting motors
- Battery disconnect switch
-
- General
-
- SAE standard rotation
- Right hand servicing
- Paint - Caterpillar yellow with high gloss black rails
Optional Equipment
-
- Air Inlet Systems
-
- Single element air cleaner
-
- Control Panels
-
- EMCP 4.4
- Controller and MV and HV power connection locations
- Load share module
- Controller voltage and current sensing groups
- Speed adjust
- Annunciator modules
- Customer interface options
- Generator temperature monitoring
- E-Stop
- Interconnect harness
- Generator harness
- Modbus monitoring of packages
- Vandal proof panel door
-
- Cooling System
-
- Package mounted radiators
- Remote radiators
- Fuel cooler
-
- Crankcase Systems
-
- Explosive relief valves
- Crankcase ventilation system
-
- Exhaust System
-
- Front housing - Standby or mission critical
- Front housing - Prime or continuous
- Exhaust collectors/manifold
- Mufflers (15, 25 and 34 dBA)
-
- Fuel System
-
- Primary fuel filter
-
- Generators And Attachments
-
- Medium voltage - 3000 Frames - 50 Hz, 3 phase, 1500 rpm, FW, PM, No of leads=6, Pitch 0.6667
- Thermostat for space heater
- Generator air cleaner
- Differential current transformers - (5, 9 and 15 kV Class)
-
- Instrumentation
-
- Pyrometer and thermocouples
-
- Lube System
-
- Lube oil heater
- Lube oil heater with Crankcase explosion relief valves
- Drain group oil pans
- Lubricating oil
- Electric prelube pumps
- Oil filters
-
- Mounting System
-
- Rubber anti-vibration mounts
- Spring type linear vibration isolators
- IBC vibration isolators - Shipped loose
-
- Special Tests / Reports
-
- Generator test report
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
- Standard genset TVA (Torsional Vibration Analysis) report
- Custom generator TVA report
- Special test charge - Engine only
- Genset fuel consumption test
- Standard engine test charge
-
- Starting / Charging System
-
- 24 Volt electric starting motor
- Air starting motor
- Air pressure regulator
- Starter location covers
- 24 Volt battery set - Dry
- 20, 35 and 50 Amp Battery chargers
- Charging alternators - Dry
- Jacket water heaters
-
- General
-
- Special paint - 3500, Colors (other than Caterpillar yellow or high performance paints)
- US aid emblem
- Service tools
- Engine barring group
- Manual
- Engine barring air powered
- control GP - air powered bar group